Atkore PG14

Allied Tube & Conduit 137 atkore.com/flexicon Flexicon To obtain EMC screening on pliable FLP conduit, the outer plastic sheath must be trimmed back prior to assembly of the fitting to ensure good electrical contact with the tapered bore of the fitting body as shown EMC Screening Using Pliable Conduit Type C Braided Fittings Our type-C braided fittings consist of an outer compression nut, an inner compression nut, an elastomeric seal, an insert and a body. Firstly place the outer compression nut on the conduit as per 1. Remove the tape securing the braid and pull back to allow the inner compression nut to be fitted as per 2. Next, fit the elastomeric seal (note the orientation) and screw the insert into the end of the conduit until this gives a secure fit as per 3. Bring the body to mate with the inner compression nut and secure. Next, bring the back shell to mate with the inner compression nut to secure the braid as per 4. Metal fittings should be tightened with grips or spanner to ensure securing and IP rating as per 5. Braid Material Part number Galv Steel LTBRDP, LTBRDP-FG, LTBRDLFH Galv Steel FB Stainless Steel LFHUBRD, FUSSB, FPRSS, FPISS, FPIHSS, FPIHRLSS, FSSBRD Tinned Copper FPRTC, FTCB STANDARD EMC SCREEN ENHANCED EMC SCREEN SUPER EMC SCREEN STANDARD EMC SCREEN ENHANCED EMC SCREEN SUPER EMC SCREEN STANDARD EMC SCREEN NHANCED EMC SCREEN SUPER EMC SCREEN Flexicon has classified EMC screening of our products as follows; Standard 50dB @ IMHz Enhanced 60dB @ IMHz Super 70dB @ IMHz LFHUBRD FPRTC EMC Screening Performance Braided Fittings - Installation 1 2 3 4 5 Technical Data EMC & Installation Instructions

RkJQdWJsaXNoZXIy NTk2NDg=